Ground Mounted
 |
- From 50kVA to 5000kVA & up to 36kV level (Higher ratings available in sMPT range)
- Hermetic or free breathing options available
- Corrugated wall as standard, flat wall with radiators and gas cushion designs upon request
- Mineral oil as standard, ester or silicone oil upon request
- Conventional losses or high efficiency design
- Real-time condition monitoring to optimize assets availability and reduce unscheduled down-time available
- On-Load Tap-Changer (OLTC), Earthing Transformers
|
Pole Mounted
 |
- From 50kVA to 500kVA, up to 36kV level
- Hermetically sealed corrugated wall design
- Mineral oil as standard, ester oil upon request
- Designed to be mounted on the pole
- Conventional losses or high efficiency design
- On-Load Tap-Changer (OLTC), Earthing Transformers
|
British Type
 |
- From 50kVA to 3150kVA & up to 36kV level (Higher ratings avaliable in MPT range)
- Hermetic or free breathing options avaliable
- Corrugated wall as standard, flat wall with radiators and gas cushion designs upon request
- Mineral oil as standard, ester or silicone oil upon request
- UKCA compliant design
|
On-Load Tap-Changer (OLTC)
 |
An On-Load Tap-Changer (OLTC) transformer is a crucial component in power distribution systems. It allows for the regulation of a transformer’s output voltage without interrupting the power supply. This function is vital for ensuring a stable and reliable power supply, particularly during fluctuations in demand or system disturbances.
- Rated power (kVA): 160, 250, 400, 630, 800, 1000
- Primary rated voltage (kV): 6.3 / 10.5 / 15.75 / 21
- Secondary rated voltage (V): 400, 410, 420
- On-load voltage regulation: ± 4 x 2.5%
- Winding connection group: Dyn5, Dyn11
- Short-circuit voltage: 4%, 4.5%, or 6%
- No-load and load losses: Compliant with EU ECO Directive Tier 2
|